Frquently Asked Questions

If you can't find the answer to your questions here, call us at +44 (0) 1256 320244 to speak with one of our knowledgeable customer service representatives. You may also fax us at +44 (0) 1256 473680, or send us an email at sales@gems-sensors.co.uk

Temperature

Please clarify the Maximum temperature specification of 55 °F (25C) above set point for a PDTF temperature switch?

Depending on the setting of the device, each one has a maximum limit based on a temperature range.

Here are the limits for each range.

Range 1: 68 -106°F max temp 161°F
Range 2: 106 -147°F max temp 202°F
Range3: 147 - 183°F max temp 228°F
Range4: 183 - 228°F max temp 283°F
Range5: 228 - 284°F max temp 339°F

Example: The limit on a setting of 75°F can be found in range 1. 68 - 106°F, maximum limit is 161°F. So the maximum temperature the sensor can see is 161F.